Protective Devices – LS, RCD, SLS and Surge Protection
🌐 Machine-translated page. The German version is authoritative.
Two Kinds of Protection
Section titled “Two Kinds of Protection”Schutzorgane (protective devices) protect either the installation (wiring, devices) or people – some protect both.
| Hazard | Protection by | Component |
|---|---|---|
| Überlast (overload) – too many loads, the cable gets warm | Tripping when the current is too high for a longer time | LS-Schalter (miniature circuit breaker), Schmelzsicherung (fuse) |
| Kurzschluss (short circuit) – L touches N or PE, huge current | Tripping within milliseconds | LS-Schalter, Schmelzsicherung, SLS |
| Fehlerstrom (residual current) / electric shock – current flows via the enclosure or a person to earth | Tripping at a small difference between outgoing and returning current | RCD (FI-Schutzschalter) |
| Überspannung (surge) – lightning, switching operations in the grid | Diverting the voltage peak to earth | SPD (Überspannungsschutzgerät, surge protective device) |

Leitungsschutzschalter (LS) on the Hutschiene (DIN rail) of a distribution board, connected at the top to a Phasenschiene (phase busbar).
Image: Pittigrilli ·License: CC0Leitungsschutzschalter (LS-Schalter)
Section titled “Leitungsschutzschalter (LS-Schalter)”The LS-Schalter (colloquially “Sicherungsautomat”) protects the Leitung (cable) against Überlast and Kurzschluss. It has two tripping mechanisms:
- Thermischer Auslöser (thermal trip) (bimetal): reacts to Überlast – slowly, depending on how far the current exceeds the rated value. 1.45 times the rated current must trip it within one hour.
- Magnetischer Auslöser (magnetic trip): reacts to Kurzschluss – instantly, as soon as the current reaches a multiple of the rated current.
The label, for example B16, means:
| Part | Meaning |
|---|---|
| B | Tripping characteristic: magnetic tripping at 3 to 5 times the rated current. Standard for dwellings. |
| C | Tripping at 5 to 10 times the rated current – for motors, devices with high inrush current. |
| D | 10 to 20 times – transformers, welding equipment. |
| 16 | Rated current 16 A |
Assignment in the flat: B10 for lighting (1.5 mm²), B16 for Steckdose (socket outlets) (2.5 mm² or 1.5 mm² for short runs), B16 3-pole for the cooker (400 V, 5×2.5 mm²), B16 or B20 for the Durchlauferhitzer (instantaneous water heater) depending on power and cross-section.
The rated current must match the Leitungsquerschnitt (cable cross-section) and the Verlegeart (installation method) – the cable must be able to carry continuously the current the LS lets through. That is a calculation, not a rule of thumb.
Schmelzsicherung
Section titled “Schmelzsicherung”The Schmelzsicherung (Neozed D01/D02 in the distribution board, NH-Sicherung in the Hausanschlusskasten (service entrance box)) is the older brother of the LS-Schalter: a wire melts on overcurrent. It is cheap, robust and can interrupt large short-circuit currents, but it must be replaced. In the Hausanschlusskasten and as a backup fuse it is still standard; in flat distribution boards the LS has displaced it.
RCD – the Fehlerstrom-Schutzschalter (FI)
Section titled “RCD – the Fehlerstrom-Schutzschalter (FI)”The RCD (Residual Current Device, in German FI-Schutzschalter) protects people. It compares the current flowing out through the Außenleiter (line conductors) with the current returning through the N (Neutralleiter, neutral conductor). Normally the sum is zero. If current flows back via another path – via the PE (Schutzleiter, protective conductor), via a defective device, via a person – a Differenz (difference) arises. From the Bemessungsdifferenzstrom IΔn (rated residual operating current) onwards, the RCD trips.
| Specification | Meaning |
|---|---|
| IΔn = 30 mA | Personal protection. Mandatory for socket outlets up to 32 A and lighting in dwellings (DIN VDE 0100-410). Tripping at the latest after 300 ms, in practice 20–40 ms. |
| IΔn = 300 mA | Fire protection, not personal protection. In agriculture, for entire installations. |
| Typ AC | detects only sinusoidal AC residual currents – not permitted in Germany |
| Typ A | additionally pulsating DC residual currents – standard for dwellings |
| Typ F | additionally mixed frequencies – washing machines, Wärmepumpe (heat pump) with Frequenzumrichter (frequency converter) |
| Typ B | additionally smooth DC residual currents – Wallbox (EV charger) (if there is no DC protection in the Wallbox), PV inverters without transformer |
| 4-pole 40 A | switches L1, L2, L3, N; the rated current (40 A) is the load capacity – the RCD does not protect against Überlast, it needs a Vorsicherung (upstream fuse) |
The Prüftaste T (test button T) generates an artificial Fehlerstrom. It must be pressed monthly (it says so on every device) – the only test the customer is allowed to do themselves.
RCBO (FI/LS combination) is an RCD and an LS in one device for a single circuit. More expensive, but if a fault occurs only one circuit goes down.
SLS – the selective main breaker
Section titled “SLS – the selective main breaker”The SLS-Schalter sits ahead of the meter in the Zählerschrank (meter cabinet) (VDE-AR-N 4100). It is the Vorsicherung for the entire Kundenanlage (customer installation) and has the E characteristic: it is selektiv (selective) with respect to the LS-Schalter behind it. In the event of a Kurzschluss in the flat, the B16 trips, not the SLS – otherwise the whole house would go dark. Typically 3×35 A or 3×50 A for a single-family house, 3×63 A with a Wärmepumpe and Wallbox.
The SLS belongs to the Zählerschrank equipment and, although it sits ahead of the meter, may be operated by the electrical contractor – it is the Freischaltpunkt (isolation point) for work on the Unterverteilung (sub-distribution board).
SPD – Überspannungsschutz
Section titled “SPD – Überspannungsschutz”Überspannungsschutzgeräte (SPD, Surge Protective Device) divert voltage peaks before they destroy devices. Three types, three locations:
| Type | Location | Against |
|---|---|---|
| Typ 1 (lightning current arrester) | Hausanschluss (service entrance) / Zählerschrank | direct lightning strike (only with a lightning protection system) |
| Typ 2 (surge arrester) | Zählerschrank or Unterverteilung | Überspannung from the grid, remote effects |
| Typ 3 (device protection) | Steckdose, device | residual voltage for sensitive electronics |
Since DIN VDE 0100-443 and -534 (2016), Überspannungsschutz (surge protection) has been mandatory in new residential buildings. The Typ 2 arrester sits in the Unterverteilung directly behind the Hauptschalter (main switch) with cables as short as possible (under 0.5 m in total) to L, N and PE.
How They Work Together in the Distribution Board
Section titled “How They Work Together in the Distribution Board”The order from the supply side: SLS (ahead of the meter) → Hauptschalter → SPD → RCD → LS → circuit. Each component has its job; none replaces another. An RCD without an LS lets the cable burn up, an LS without an RCD lets 20 mA flow undisturbed through a person. How this is actually wired up is shown in the guide Building an Unterverteilung.
Test Yourself
Section titled “Test Yourself”🧠 Test yourself
Sources
- DIN VDE 0100-410:2018-10 – Protection against electric shock (RCD ≤ 30 mA for socket outlets up to 32 A and lighting in dwellings)
- VDE-AR-N 4100:2026-04 – Technical connection rules for low voltage (SLS ahead of the meter)
- Elektro+ – Standards, directives and requirements for electrical installations in residential buildings (DIN 18015, surge protection)
- Wikimedia Commons – Photo of fuse box with ABB Leitungsschutzschalter (CC0, Pittigrilli)